Revision 7.1b Page 21 of 31
Mercury Coldroom Panel Installation Guide
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
IP-r
To configure the communication module for IP-r, set the three rotary switches to give each controller a unique identifier. The module
should then be connected to the controller and the network.
2. nEt. From the function menu you can now select nEt
Press enter and the display will show “IP-r”, press enter
You can now view only the address given by the DHCP server
Mercury Hub
Please refer to the Mercury Hub user guide, which can be obtained from the RDM website, for information regarding connecting a
controller to a network via the Mercury Hub.
Viewing
Apart from setting up the controller, you can also view the status of the inputs and outputs.
1. IO. View Inputs / Outputs and States
a. From the function menu, select “IO”, press enter
b. You can now scroll through the IO tables as set out below. The tables you view will depend on the controller type
configuration.
Input/Output table for Coldroom Panel with Compressor/LLV option
Range (dependant on probe type)
o
C (
o
F )
-42 to 60 (-56.2 to 262.4) PT 1000 only
0 (None), 1 (Internal),
2 (External), 3 (Network),
4 (Display), 5 (Timed)