Revision 7.1b Page 9 of 31
Mercury Coldroom Panel Installation Guide
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
Input/Output Allocation Tables
The following tables indicate; on a controller type basis, the functions of the inputs and outputs. Also shown are the digital inputs that are
derived by switching in a fixed value resistor across the input
Inputs and Outputs
This unit must be Earthed
Connection on the isolator
Connection on the isolator
On the PCB (Non-isolator version)
On the PCB (Non-isolator version)
Defrost Termination (if used)
Logging Probe (If fitted)
N/O and N/C (N/O only on EEV)
See Specification for further details
See Specification for further details
See Specification for further details
See Specification for further details
Always Live (heater mats)
See Specification for further details
See Specification for further details
N/O, N/C & Common (Volt-free)
See Specification for further details
Note: -
For PT1000 probes, jumpers; LK1 & LK2, are in the outer positions for the additional switched resistor functions to operate.
For NTC probes, jumpers; LK1 & LK2, are in the inner positions for the additional switched resistor functions to operate.
Digital Inputs
Plant fault 1/External defrost input*
Plant Fault 1/External defrost input*
Air off Temperature Probe
* For PT1000 probes, use 820 Ohm switched resistors to activate input.
For NTC2K and NTC2K25 probes, use 590 Ohm switched resistors to activate input.