Mercury Plant Controller Installation Guide
Reduces the inverter output by this amount when the timer is
not in its night zone.
Pressure set-point to disable the day reduction feature. Day
reduction is disabled above this level and enabled below it.
Sets the output level of the inverter if the transducer fails
Selects between Fixed, Floating or Drop Leg control for
Condenser control only.
Fixed uses the set-point parameter as its target (P-20/40)
with the corresponding pressure transducer.
Floating uses the temperature of a selected probe converted
to a pressure as the set-point along with the corresponding
pressure transducer.
Drop leg uses the temperature of probe mounted on the drop
leg to calculate control pressure and uses the set-point
parameter as its target (P-20/40).
Selects the probe that measures the “floating” temperature
(Note : This would be fitted to the Air On of the Condenser)
See Note Floating Head Pressure
Selects which probe is used to measure Drop Leg
temperature. See Note Drop Leg
Used to program the temperature to pressure conversion for
floating pressure use.
Used to program the temperature to pressure conversion for
floating pressure use.
Used to program the temperature to pressure conversion for
floating pressure use.
Used to program the temperature to pressure conversion for
floating pressure use.
Used to program the temperature to pressure conversion for
floating pressure use.
Used to program the temperature to pressure conversion for
floating pressure use.
Stops the floating pressure target from going below this level
Stops the floating pressure target from going above this level
Used to set a condenser differential, which is added to the
incoming temperature to produce a “floating” set-point
Set to “On” to enable Condenser Split feature.
If outside ambient air temperature falls to this value then the
condenser split relay will come on. Note the Condenser Float
temperature probe is used as the air temperature reference.
Sect 1 / 2 Split Temp Diff
Diff above for the split temp feature (P-430/431). If outside
ambient air temperature rises above Sect 1/2 Split Temp
parameter plus Sect 1/2 Split Temp Diff parameter then the
Condenser split relay will go off
Sect 1 / 2 Split Pressure
If the discharge pressure rises above this setting then the
condenser split relay will be forced off regardless of
temperature.
Sect 1 / 2 Split Pressure Diff
Diff below parameter for Split Pressure feature (P-434/435).
If the pressure for Section1/2 falls below Sect 1/2 Split
Pressure setpoint plus Sect 1/2 Split Pressure Diff parameter
then the condenser split relay will return to normal operation
(status depends on P-430/431).
Enable for Heat Reclaim. See : Relay Outputs
0 = Off (Not Used)